Informações Tećnicas
- Configuration: Wall mounted paralleling control system that monitors and controls a single generator and a single utility.
- Modes of Operation: Utility Import, Export, and base load operations, Peak shaving, and Emergency Standby. Closed Transition to/from Generator Power
- Application: LV and MV (208V-32kV)
Mais informações
Technical Summary
- Configuration: Wall mounted paralleling control system that monitors and controls a single generator and a single utility.
- Modes of Operation: Utility Import, Export, and base load operations, Peak shaving, and Emergency Standby. Closed Transition to/from Generator Power
- Application: LV and MV (208V-32kV)
Generator Protective Devices
- ANSI Protective Devices: 15/25. 27/59, 81 O/U, 32, 40, 50, 51
Utility Protective Devices
- ANSI Protective Devices: 15/25. 27/59, 81 O/U, 32, 40, 47, 51, 86
Environmental Parameters
- Certifications: IBC, CBC, UBC, & OSHPD Certified
- Control Panel Enclosure: NEMA 1 or NEMA 3R Freestanding Construction
- Operating Temperature: 0-50°C
- Storage Temperature: -20°C to +60°C
- Low Voltage Standards: NEMA SG-5, CSA,ANSI C37.51, ANSI C37.20.1, UL1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70
- Medium Voltage Standards: NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110